Remote output function (REM, Pr. 495 to Pr. 497)

You can utilize the on/off of the inverter's output signals instead of the remote output terminal of
the programmable logic controller.
Pr.
Name
No.
Remote output
495
selection
Remote output
496
data 1
Remote output
497
data 2
The above parameters can be set when Pr. 160 "User group read selection" = 0.
The above parameters allow its setting to be changed during operation in any operation
mode even if "0" (initial value) is set in Pr. 77 "Parameter write selection".
The output terminal can be turned on/off depending onthe Pr. 496 or Pr. 497 setting. The remote
output selection can be controlled on/off by computer link communication from the PU connector
or by communication from the communication option.
Set "96 (positive logic) or 196 (negative logic)" to any of Pr. 190 to Pr. 192 "Output terminal func-
tion selection", and assign the remote output (REM) signal to the terminal used for remote out-
put.
FR-E700 EC
Initial
Setting
Description
Value
Range
Remote output data
0
clear at powering off
Remote output data
1
retention at powering
off
0
Remote output data
10
clear at powering off
Remote output data
11
retention at powering
off
0
0–4095
Refer to Fig. 6-65
0
0–4095
Function assignment of external terminals
Parameters referred to
190–192
Remote output data
clear at inverter
reset
Remote output data
retention at inverter
reset
Refer to
Section
Output terminal
6.10.5
function selection
6 - 133