Remote Output Function (Rem Signal, Pr. 495 To Pr. 497) - Mitsubishi Electric FR-F740-00023-EC Instruction Manual

Frequency inverter
Hide thumbs Also See for FR-F740-00023-EC:
Table of Contents

Advertisement

3.9.8

Remote output function (REM signal, Pr. 495 to Pr. 497)

You can utilize the on/off of the inverter's output signals instead of the remote output terminal of the
programmable logic controller.
Parameter
Name
Number
495
Remote output selection
496 *
Remote output data 1
497 *
Remote output data 2
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 146)
* The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in
Pr. 77 Parameter write selection.
<Remote output data>
Pr. 496
b11
Pr. 497
b11
*1
As desired (always 0 when read)
*2
Y0 to Y6 are available only when the extension output option (FR-
A7AY) is fitted
*3
RA1 to RA3 are available only when the relay output option (FR-
A7AR) is fitted
Example)When "96" (positive logic) is set to Pr. 190 RUN terminal function selection and "1" (H01) is set to Pr. 496,
the terminal RUN turns on.
ON/OFF example for positive logic
Pr.495 = 0
Pr.495 = 1
Power
Power
OFF
supply
supply
OFF REM
REM
REM signal clear
REMARKS
⋅ The output terminal where the REM signal is not assigned using any of Pr. 190 to Pr. 196 does not turn on/off if 0/1 is set to the
terminal bit of Pr. 496 or Pr. 497 . (It turns on/off with the assigned function.)
⋅ When the inverter is reset (terminal reset, reset request through communication), Pr. 496 and Pr. 497 values turn to "0". When Pr.
495 = "1", however, they are the settings at power supply-off. (The settings are stored at power supply-off.)
CAUTION
⋅ When Pr. 495 = "1", take such a step as to connect R1/L11, S1/L21 and P/+, N/- to ensure that control power will be retained to
some degree. If you do not take such a step, the output signals provided after power-on are not guaranteed.
♦ Parameters referred to ♦
Pr. 190 to Pr. 196 (output terminal function selection)
Initial Value
Setting Range
0
0
0
⋅ The output terminal can be turned on/off depending on
the Pr. 496 or Pr. 497 setting. The remote output
b0
selection can be controlled on/off by computer link
communication from the PU connector or RS-485 port
or by communication from the communication option.
⋅ Set "96" (positive logic) or "196" (negative logic) to any
of Pr. 190 to Pr. 196 (output terminal function selection),
and assign the remote output (REM) signal to the
b0
terminal used for remote output,
⋅ When you refer to the above diagram and set 1 to the
terminal bit (terminal where the REM signal has been
assigned) of Pr. 496 or Pr. 497, the output terminal
turns on (off for negative logic). By setting 0, the
output terminal turns off (on for negative logic).
⋅ When Pr. 495 = "0" (initial value), performing a power
supply reset (including a power failure) clears the REM
signal output. (The ON/OFF states of the terminals are
as set in Pr. 190 to Pr. 196.) The Pr. 496 and Pr. 497
OFF
settings are also "0".
Inverter
reset time
When Pr. 495 = "1", the remote output data before power
(about 1s)
supply-off is stored into the EEPROM, so the signal
ON
output at power recovery is the same as before power
supply-off. However, it is not stored when the inverter is
REM signal held
reset
communication).
(See the chart on the left)
Refer to page 96
Function assignment of external
terminal and control
Remote output data clear at powering
0
off
Remote output data retention even at
1
powering off
0 to 4095
Refer to the following diagram.
0 to 4095
(terminal
reset,
reset
Description
request
through
103
Pr.343
page 179
Pr.503
page 219