Mitsubishi Electric FR-E700 Instruction Manual page 414

Frequency inverter
Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Special operation
Reverse action
Increases the manipulated variable fi (output frequency) if deviation X = (set point − measured
value) is positive, and decreases the manipulated variable if deviation is negative.
Set point
Fig. 6-136: Heater
Forward action
Increases the manipulated variable (output frequency) if deviation X = (set point − measured val-
ue) is negative, and decreases the manipulated variable if deviation is positive.
Set point
Fig. 6-137: Cooling
Relationships between deviation and manipulated variable (output frequency).
Reverse action
Forward action
Tab. 6-102: Relationships between deviation and manipulated variable
6 - 274
X>0
+
Cold → fi increased
Hot → fi decreased
X<0
Feedback signal
(measured value)
X>0
+
Too Cold → fi decrease
Hot → fi increase
X<0
Feedback signal
(measured value)
Deviation
Measured value
Measured value
Deviation
Deviation
Positive
Parameter
Set point
t
I000047C
Set point
t
I000048C
Negative