Mitsubishi Electric FR-E700 Instruction Manual page 239

Frequency inverter
Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Parameter
Operation frequency setting (Pr. 10)
When the frequency at which the DC injection brake operates is set to Pr. 10, the DC injection
brake is operated when this frequency is reached during deceleration.
100
Operation time setting (Pr. 11)
Use Pr. 11 to set the duration period the DC injection brake is applied.
When the motor does not stop due to large load moment (J), increasing the setting produces an
effect.
When Pr. 11 = 0s, the DC injection brake is not operated. (At a stop, the motor coasts.)
FR-E700 EC
Pr. 10
Pr. 12
Pr. 11
Motor brake and stop operation
Fig. 6-41:
When Pr. 11 is set to a value between 0.1
and 10s
t
t
I000007C
6 - 99

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e720sFr-e740

Table of Contents