Mitsubishi Electric FR-E700 Instruction Manual page 316

Frequency inverter
Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Frequency setting by analog input (terminal 2, 4)
Refer to the following table and set Pr. 73 and Pr. 267. The half-tone screened areas indicate
the main speed setting.
Pr. 73
0
1
(initial
value)
10
11
0
1
(initial
value)
10
11
Tab. 6-46: Setting of parameter 73 and 267
The terminal used for the AU signal input, set "4" in Pr. 178 to Pr. 184 "Input terminal function
selection" to assign functions.
NOTES
Turn the AU signal on to make terminal 4 valid.
Make sure that the parameter and switch settings are the same. Different setting may cause
a fault, failure or malfunction.
Use Pr. 125 (Pr. 126) "Frequency setting gain" to change the maximum output frequency at
input of the maximum output frequency command voltage (current). At this time, the com-
mand voltage (current) need not be input. Also, the acceleration/deceleration time, which is a
slope up/down to the acceleration/deceleration reference frequency, is not affected by the
change in Pr. 73 setting.
Changing the terminal assignment using Pr. 178 to Pr. 184 "Input terminal function selec-
tion" may affect the other functions. Make setting after confirming the function of each termi-
nal.
6 - 176
Terminal 2
AU signal
0–10V
0–5V
OFF
0–10V
0–5V
ON
Terminal 4
According to Pr. 267:
0: 4–20mA (initial value)
1: 0–5V
2: 0–10V
Parameter
Polarity Reversible
No
Yes
No
Yes