Mitsubishi Electric FR-E700 Instruction Manual page 153

Frequency inverter
Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Parameter
Parameter
Func-
Name
tion
Operation mode
79
selection
Communication start-
340
up mode selection
80
Motor capacity
81
Number of motor poles
Speed control gain
(advanced magnetic
89
flux vector)
Control method selec-
800
tion
Tab. 6-1:
Parameter overview (13)
These parameters are communication parameters that are not cleared when parameter
clear (all clear) is executed from RS-485 communication. (Refer to section 6.19 for RS-485
communication) Note that when using a three-phase power input specification model,
Pr. 345 and Pr. 346 are set back to initial values.
FR-E700 EC
Incre-
Initial
Setting
ments
value
range
0
1
2
3
1
0
4
6
7
0
1
1
0
10
0.1–15kW
0.01kW
9999
9999
2/4/6/8/10
12/14/16/
1
9999
18/20
9999
0–200%
0.1%
9999
9999
20
1
20
30
Description
External/PU switch over mode
Fixed to PU operation mode
Fixed to External operation mode
External/PU combined operation
mode 1
External/PU combined operation
mode 2
Switch-over mode
External operation mode
(PU operation interlock)
As set in Pr. 79.
Started in the network operation
mode.
Started in the network operation
mode. Operation mode can be
changed between the PU operation
mode and network operation
mode from the operation panel.
Set the applied motor capacity.
V/f control is performed
Set the number of motor poles.
X18 signal
Set 10 + number
ON: V/f con-
of motor poles
trol
V/f control is performed
Motor speed fluctuation due to
load fluctuation is adjusted during
advanced magnetic flux vector
control.
100% is a referenced value.
Gain matching with the motor set
in Pr. 71.
Advanced
magnetic flux
vector control Set a value other
than "9999" in
General-pur-
Pr. 80 and Pr. 81.
pose mag-
netic flux
vector control
Parameter overview
All
Para-
Para-
Para-
meter
meter
meter
copy
clear
clear
Refer
to
page
✔: enabled
—: disabled
6-198
6-210
6-36
6 - 13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e720sFr-e740Fr-e700 seriesFr-e720s ecFr-e740 ec

Table of Contents