Parameter
Power failure stop mode (Pr. 261 = 1)
If power is restored during power failure deceleration, deceleration to a stop is continued and the
inverter remains stopped. To restart, turn off the start signal once, then turn it on again.
Fig. 6-82: Power restoration
When automatic restart after instantaneous power failure is selected (Pr. 57 ≠ 9999), power
NOTES
failure stop function is made invalid and automatic restart operation after instantaneous
power failure is made valid.
After a power failure stop, the inverter will not start even if the power is restored with the start
signal (STF/STR) input. After switching on the power, turn off the start signal once and then
on again to make a start.
Fig. 6-83: Restart at power restoration
FR-E700 EC
Power
supply
During deceleration at
Output
occurrence of power failure
frequency
Power
supply
Not started as inverter is
stopped due to power
failure
Operation selection at power failure
During stop at
occurrence of
power failure
Time
Turn off STF once to make
acceleration again
ON
Output
frequency
OFF
ON
I001815E
I001175E
6 - 163