Control circuit specifications
Using an external power supply
● Sink logic type
Use terminal PC as a common terminal to prevent a malfunction caused by undesirable
current. (Do not connect terminal SD of the inverter with terminal 0V of the external power
supply. When using terminals PC-SD as a 24V DC power supply, do not install a power
supply in parallel in the outside of the inverter. Doing so may cause a malfunction due to
undesirable current.)
● Source logic type
When using an external power supply for transistor output, use terminal SD as a common
to prevent misoperation caused by undesirable current.
3 - 22
AY40
Inverter
Current
AY80
Inverter
Current
Fig. 3-12:
Using an external power supply in connection
with the outputs of a PLC
Fig. 3-13:
Using an external power supply in connection
with the outputs of a PLC
Wiring
I001030E
I001031E