When automatic restart after instantaneous power failure has been
selected, the motor and machine will start suddenly (after the reset time
has elapsed) after occurrence of an instantaneous power failure.
Stay away from the motor and machine.
When you have selected automatic restart after instantaneous power
failure, apply the supplied CAUTION seals in easily visible places.
When the start signal is turned off or the
cushion time for automatic restart after instantaneous power failure,
deceleration starts after the automatic restart cushion time set in Pr. 58
"cushion time for automatic restart after instantaneous power failure"
has elapsed.

" " Remote setting function selection (Pr. 59)

4.2.23 Remote setting function selection (Pr. 59)
Pr. 59 "remote setting function selection"
If the operator panel is located away from the
control box, you can use contact signals to
perform continuous variable-speed operation,
without using analog signals.
! By merely setting this parameter, you can use
the acceleration, deceleration and setting clear
functions of the motorized speed setter (FR-FK).
! When the remote function is used, the output frequency of the inverter can be
compensated for as follows:
External operation mode
PU operation mode
Parameter
Factory
Number
Setting
59
0
Acceleration (RH)
Deceleration (RM)
Clear (RL)
Forward rotation (STF)
Power supply
Note: External operation frequency or PU operation frequency other than multi-speed
CAUTION
Frequency set by RH/RM operation plus built-in
frequency setting potentiometer or external analog
frequency command
Frequency set by RH/RM operation plus PU's digitally-
set frequency
Setting
Range
0, 1, 2
(Note)
0Hz
ON
ON
ON
ON
ON
STOP
key is pressed during the
RESET
Related parameters
Pr. 1 "maximum frequency"
Pr. 7 "acceleration time"
Pr. 8 "deceleration time"
Pr. 18 "high-speed maximum
frequency"
Pr. 44 "second acceleration/
deceleration time"
Pr. 45 "second deceleration time"
ON
ON
ON
ON
93
PARAMETERS
When Pr. 59=1
When Pr. 59=2
ON
ON
4