Operation selection at power failure
6.12.2

Power failure-time deceleration-to-stop function (Pr. 261)

When a power failure or under voltage occurs, the inverter can be decelerated to a stop or can
be decelerated and re-accelerated to the set frequency.
Pr.
Name
No.
Power failure stop
261
selection
The above parameter can be set when Pr. 160 "User group read selection" = 0.
Parameter setting
When Pr. 261 is set to "1" or "2", the inverter decelerates to a stop if an undervoltage or power
failure occurs.
Operation outline of deceleration to stop at power failure
When undervoltage or power failure has occurred, the output frequency is decreased and con-
trolled so that the converter circuit (DC bus) voltage is constant and decreased to 0Hz to stop.
Fig. 6-81: Parameters for stop selection at power failure
6 - 162
Initial
Setting
Description
Value
Range
Coasting to stop when under voltage or
0
power failure occurs, the inverter output
is shut off.
When under voltage or a power failure
1
occurs, the inverter can be decelerated to
0
a stop.
When under voltage or a power failure
occurs, the inverter can be decelerated to
2
a stop.
If power is restored during a power fail-
ure, the inverter accelerates again.
Power
Output fre-
quency
ON
OFF
Parameter
Parameters referred to
57
Restart coasting
time
190–192
Output terminal
function selection
Time
Refer to
Section
6.12.1
6.10.5
I001814E