Parameter
Dancer control block diagram
setting point
Fig. 6-143: Dancer control block diagram
The main speed can be selected from all operation mode such as external (analog voltage
input, multi-speed), PU (digital frequency setting), communication (RS-485, CC-Link).
Set point and measured value of PID control
Set point
Measured
value
Tab. 6-105: Set point and measured value of PID control
NOTES
Changing the terminal function using any of Pr.178 to Pr.184 may affect the other functions.
Make setting after confirming the function of each terminal.
When the Pr. 267 setting was changed, check the voltage/current input switch setting. Differ-
ent setting may cause a fault, failure or malfunction. (Refer to page 6-175 for setting.)
FR-E700 EC
Main speed
command
PID
deviation
PID control
Dancer roll
Pr. 133
PID set point
PID feedback
Convert to
0 to 100%
Terminal 4
Input
Pr. 133
When measured value is
input as current (4 to
20mA).
When measured value is
input as voltage (0 to ±5V
or 0 to ±10V).
Acceleration/deceleration
of main speed
Potentiometer
Input Signal
0–100%
4mA ... 0%, 20mA ... 100%
0V ... 0%, 5V ... 100%
0V ... 0%, 10V ... 100%
Special operation
Target frequency
Acceleration/
Limit
deceleration
M
3~
Dancer roll position detection
Current/Voltage Input
Pr. 267
Switch
0
1
2
I001840E
6 - 283