Parameter overview
Parameter
Func-
Name
tion
PU display language
145
selection
146
Parameter for manufacturer setting. Do not set.
Output current detec-
150
tion level
Output current detec-
151
tion signal delay time
Zero current detection
152
level
Zero current detection
153
time
156
Refer to Pr. 22
157
158
Refer to Pr. 52
User group read
160
selection
User group registered
172
display/batch clear
User group registration
173
User group clear
174
Tab. 6-1:
Parameter overview (20)
6 - 20
Incre-
Initial
Setting
ments
value
range
0
1
2
3
1
1
4
5
6
7
0.1%
150%
0–200%
0.1s
0s
0–10s
0.1%
5%
0–200%
0.01s
0.5s
0–1s
0
1
0
1
9999
(0–16)
1
0
9999
1
9999
0–999/9999
1
9999
0–999/9999
Description
Japanese
English
German
French
Spanish
Italian
Swedish
Finnish
Set the output current detection
level. 100% is the rated inverter
current.
Set the output current detection
period. Set the time from when the
output current has risen above the
setting until the output current
detection signal (Y12) is output.
Set the zero current detection
level. Suppose that the rated
inverter current at the specified
overload capacity is 100%.
Set this parameter to define the
period from when the output cur-
rent drops below the Pr. 152 value
until the zero current detection
signal (Y13) is output.
Simple mode and extended mode
parameters can be displayed.
Only parameters registered in the
user group can be displayed.
Only the simple mode parameters
can be displayed
Displays the number of cases reg-
istered as a user group (reading
only).
Batch clear the user group regis-
tration
Set the parameter numbers to be
registered to the user group.
Read value is always "9999".
Set the parameter numbers to be
cleared from the user group.
Read value is always "9999".
Parameter
All
Para-
Para-
Para-
meter
meter
meter
copy
clear
clear
Refer
to
page
✔: enabled
—: disabled
6-306
6-131
6-195

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e720sFr-e740Fr-e700 seriesFr-e720s ecFr-e740 ec

Table of Contents