PU operation mode
5.2.4

Perform frequency setting by analog voltage input

In this type of setpoint selection a potentiometer is connected to the frequency inverter. The po-
tentiometer is supplied with a voltage of 5V through terminal 10 of the frequency inverter.
Fig. 5-17: Frequency setting by analog voltage input
● Pr. 79 "Operation mode selection" must be set to "4" (external/PU combined operation
mode 2).
● Use the RUN key to give a start command.
5 - 26
Power supply
Frequency setting
potentiometer
(1kΩ/2W)
Inverter
Motor