Limit The Maximum And Minimum Output Frequency (Pr. 1, Pr. 2) - Mitsubishi Electric FR-F 700 EC Instruction Manual

Hide thumbs Also See for FR-F 700 EC:
Table of Contents

Advertisement

4.3 Limit the maximum and minimum output frequency (Pr. 1, Pr. 2)

Parameter
Name
Number
1
Maximum frequency
2
Minimum frequency
Changing example
Limit the frequency set by the potentiometer,
etc. to 50Hz maximum.
(Set "50"Hz in Pr. 1 Maximum frequency.)
1.
Screen at powering on
The monitor display appears.
2.
Press
to choose the PU operation
mode.
3.
Press
setting mode.
4.
5.
Press
to read the currently set value.
"
"(initial value) appears.
6.
Turn
to change it to the set
value "
7.
Press
to set.
REMARKS
· The output frequency is clamped by the Pr. 2 setting even if the set frequency is lower than the Pr. 2 setting (The frequency will
not decrease to the Pr. 2 setting.)
Note that Pr. 15 Jog frequency has higher priority than the minimum frequency.
· When the Pr. 1 setting is changed, frequency higher than the Pr. 1 setting can not be set by
· When performing a high speed operation at 120Hz or more, setting of Pr. 18 High speed maximum frequency is necessary.
(Refer to
Instruction Manual (applied).)
If the Pr. 2 setting is higher than the Pr. 13 Starting frequency value, note that the motor will run at the set
frequency according to the acceleration time setting by merely switching the start signal on, without entry of
the command frequency.
Initial Value
01160 or less
01800 or more
Operation
to choose the parameter
Pr. 1) appears.
".
· By turning
, you can read another parameter.
· Press
to show the setting again.
· Press
twice to show the next parameter.
CAUTION
Limit the maximum and minimum
output frequency (Pr. 1, Pr. 2)
Setting
Range
120Hz
0 to 120Hz
60Hz
0Hz
0 to 120Hz
Output frequency
(Hz)
Pr.1
Pr.18
Pr.2
0
(4mA)
Clamped at the
minimum frequency
Display
PU indication is lit.
Flicker ··· Parameter setting complete!!
Description
Set the upper limit of the output
frequency.
Set the lower limit of the output
frequency.
Clamped at the
maximum frequency
Frequency setting
5, 10V
(20mA)
The parameter
number read
previously appears.
.
4
51

Advertisement

Table of Contents
loading