Main circuit connection

3.3
Main circuit connection
3.3.1

Specification of main circuit terminal

Terminal
R/L1,
S/L2,
T/L3
U, V, W
+, PR
+, −
+, P1
Tab. 3-2: Specification of main circuit terminal
When using single-phase power input, terminals are L1, N.
3 - 6
Name
Description
AC power input
Connect to the commercial power supply.
Keep these terminals open when using the high power factor converter
(FR-HC) or power regeneration common converter (FR-CV).
Inverter output
Voltage ouput of the inverter
(3~, 0V–power supply voltage, 0.2–400 Hz)
Brake resistor con-
Connect a brake transistor (FR-ABR, MRS) across terminals + and PR.
nection
(The brake resistor can not be connected to the FR-E720S-008 and 015.)
Brake unit connection Connect the brake unit (FR-BU2), power regeneration common converter
(FR-CV) or high power factor converter (FR-HC).
DC reactor
Remove the jumper across terminals + and P1 and connect a DC reactor.
connection
PE
For earthing the inverter chassis. Must be earthed.