Special operation
I/O signals and parameter setting
Set "20, 21, 50, 51, 60 or 61" in Pr. 128 to perform PID operation.
Set "14" in any of Pr. 178 to Pr. 184 "Input terminal function selection" to assign PID control
selection signal (X14) to turn the X14 signal on.
When the X14 signal is not assigned, only the Pr. 128 setting makes PID control valid.
Enter the set point using the inverter terminal 2 or Pr. 133 and enter the measured value to
terminal 4.
NOTES
When Pr. 128 = "0" or X14 signal is off, normal inverter operation is performed without PID
action.
Turning ON/OFF of bit of the terminal, to which X14 signal is assigned through network as
RS-485 communication, enables PID control.
Signal
X14
PU
Commu-
nication
Tab. 6-103: I/O signals and parameter settings (1)
6 - 276
Terminal
Function
used
Depending
PID control
on
selection
Pr. 178–184
Set point input Enter the set point for PID control. Pr. 128 = 20, 21; Pr. 133 = 9999
2
2
Set point input Set the set value (Pr. 133) from
Measured
value input
4
4
Deviation
value input
Set value,
measured
value input
Description
Turn on X14 to perform PID
control.
0–5V.......... 0–100%
0–10V........ 0–100%
the operation panel.
Input the signal from the detector
(measured value signal).
4–20mA..... 0–100%
0–5V.......... 0–100%
0–10V........ 0–100%
Input the deviation value from
LONWORKS , CC-Link communi-
cation.
Input the set value and measured
value from LONWORKS , CC-Link
communication
Parameter
Parameter Setting
Set "14" to any of
Pr. 178 to Pr. 184.
Pr. 73 = 1
, 11
Pr. 73 = 0, 10
Pr. 128 = 20, 21;
Pr. 133 = 0–100%
Pr. 128 = 20, 21
Pr. 267 = 0
Pr. 267 = 1
Pr. 267 = 2
Pr. 128 = 50, 51
Pr. 128 = 60, 61