Mitsubishi Electric FR-E700 Instruction Manual page 292

Frequency inverter
Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Operation selection at power failure
Pr.
Name
No.
Regenerative function
30
selection
57
Restart coasting time
58
Restart cushion time
Auto tuning setting/
96
status
Automatic restart after
162
instantaneous power
failure selection
Stall prevention opera-
165
tion level for restart
298
Frequency search gain
Rotation direction
299
detection selection at
restarting
Acceleration time at a
611
restart
The above parameters can be set when Pr. 160 "User group read selection" = 0.
6 - 152
Initial
Setting
Description
Value
Range
The motor starts at the starting fre-
0/1
quency when MRS (X10) turns on then
off.
0
Restart operation is performed when
2
MRS (X10) turns on then off
FR-E720S-080 or less,
FR-E740-040 or less ..................... 1 s
0
FR-E720S-110,
FR-E740-060 to 170...................... 2 s
FR-E740-230 and 300................... 3 s
9999
Set the waiting time for inverter-trig-
0.1–5s
gered restart after an instantaneous
power failure.
9999
No restart
1s
0–60s
Set a voltage starting time at restart.
0
Offline auto tuning is not performed
Advanced magnetic flux vector control
Offline auto tuning is performed with-
1
out motor running (all motor con-
stants) (Refer to section 6.3.2.)
For general-purpose magnetic flux vec-
tor control
0
11
Offline auto tuning is performed with-
out motor running (motor constants
(R1) only) (Refer to section 6.3.3.)
Offline auto tuning (tuning performed
without motor running) for V/f control
21
and automatic restart after instantane-
ous power failure (with frequency
search)
0
With frequency search
No frequency search:
The output voltage is increased until
1
the preset frequency is reached, irre-
spective of the current motor speed.
0
10
Frequency search at every start
On every start the output voltage is
increased until the preset frequency
11
reached, irrespective of the current
motor speed.
Consider the rated inverter current
according to the overload capacity as
150%
0–200%
100% and set the stall prevention oper-
ation level during restart operation.
When offline auto tuning is performed
under V/f control, frequency search
gain necessary for frequency search for
0–32767
automatic restart after instantaneous
9999
power failure is set as well as the motor
constants (R1).
Uses the Mitsubishi motor (SF-JR, SF-
9999
HR, SF-JRCA, SF-HRCA) constants
0
Without rotation direction detection
1
With rotation direction detection
9999
When Pr. 78 = "0", the rotation direction
is detected.
9999
When Pr. 78 = "1","2", the rotation direc-
tion is not detected.
Acceleration time to reach the accelera-
0–3600s
tion time reference frequency at a
restart.
9999
Acceleration time for restart is the nor-
9999
mal acceleration time (e.g. Pr. 7)
Parameter
Parameters referred to
7
Acceleration time
21
Acceleration/
deceleration time
increments
13
Starting frequency
65
Retry selection
67–69
Retry function
71
Applied motor
78
Reverse rotation
prevention selec-
tion
178–184
Input terminal
function selection
Refer to
Section
6.7.1
6.7.1
6.7.2
6.13.1
16.13.1
6.8.2
6.17.3
6.10.1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e720sFr-e740Fr-e700 seriesFr-e720s ecFr-e740 ec

Table of Contents