Mitsubishi Electric FR-E700 Instruction Manual page 236

Frequency inverter
Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Selection and protection of a motor
To enter the Pr. 90 and Pr. 94 motor constants in [mH]
Set Pr. 71 according to the motor used:
Motor
Mitsubishi standard motor,
Mitsubishi high efficiency motor
Mitsubishi constant-torque motor
Tab. 6-21: Motor selection
For other settings of Pr. 71, refer to section 6.8.2.
In the parameter setting mode, read the following parameters and set desired values.
Calculate the Pr. 94 value from the following formula.
Pr. 94
U
R1: Primary resistance
R2: Secondary resistance
l1: Primary leakage inductance
l2: Secondary leakage inductance
M: Excitation inductance
S: Slip
L1 = l1 + M: Primary inductance
L2 = l2 + M: Secondary inductance
6 - 96
2
M
×
1
100 [%]
=
-------------------- -
×
L1
L2
R1
l1
l2
M
R2/S
SF-JR
SF-HR
SF-JRCA 4P
SF-HRCA
Fig. 6-40:
Motor equivalent circuit diagram
Parameter
Pr. 71
0
40
1
50
I001556E

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e720sFr-e740

Table of Contents