Control circuit specifications
Output signals
Terminal
Tab. 3-10: Output signals
Communication
Name
PU connector
USB connector
Tab. 3-11: Communication signals
3 - 16
Name
Relay output
A, B, C
(alarm output)
RUN
Inverter running
Frequency
FU
detection
Open collector
SE
output common
Analog voltage
AM
output
Description
With the PU connector, communication can be
made through RS-485.
The FR Configurator can be operated by con-
necting the inverter to the personnel computer
through USB.
Description
The alarm is output via relay contacts. The
block diagram shows the normal operation and
voltage free status. If the protective function is
activated, the relay picks up.
B
A
C
Switched low when the inverter output fre-
quency is equal to or higher than the starting
frequency (initial value 0.5Hz).
Switched high during stop or DC injection
brake operation.
The output is switched low once the output fre-
quency exceeds a value preset in Pr. 42 (or
43). Otherwise the FU output is switched high.
Reference potential for the signals RUN and
FU. This terminal is isolated from the reference
potential of the control circuit SD.
Select one e.g. output fre-
quency from monitor items.
The output signal is propor-
tional to the magnitude of
the corresponding monitor-
ing item.
Not output during inverter
reset.
Rated
Specifications
Contact
capacity:
230V AC/0.3A
(Power
factor: 0.4) or
30V DC/0.3A
Permissible
load:
24V DC (max.
27V DC), 0.1A
(A voltage drop
is 3.4V maxi-
mum when the
signal is on.)
Output signal:
0–10V DC
Permissible
Output item:
load current:
Output
1 mA
frequency
(load imped-
(initial setting)
ance:
≥ 10kΩ)
Resolution:
8 bit
Specification
Conforming standard: EIA-
485 (RS-485)
Transmission format:
Multidrop
Communication speed:
4800 to 38400bps
Overall lenght: 500m
Interface: conforms to
USB1.1
Transmission speed: 12Mbps
Connector: USB mini B con-
nector (receptacle mini B
type)
Wiring
Refer to
6-124
6-146
Refer to
3-23,
6-221
3-25,
6-269