Function assignment of external terminals
Output frequency detection (FU, Pr. 42, Pr. 43)
The output frequency detection signal (FU) is output when the output frequency reaches or ex-
ceeds the Pr. 42 setting. This function can be used for electromagnetic brake operation, open
signal, etc.
When the detection frequency is set to Pr. 43, frequency detection for reverse operation use only
can also be set. This function is effective for switching the timing of electromagnetic brake op-
eration between forward rotation (rise) and reverse rotation (fall) during vertical lift operation,etc.
When Pr. 43 ≠ 9999, the Pr. 42 setting is used for forward rotation and the Pr. 43 setting is used
for reverse rotation.
Fig. 6-62: Frequency detection for forward and reverse rotation
NOTES
The FU signal is assigned to the terminal FU in the initial setting. The FU signal can also be
assigned to the other terminal by setting "4 (positive logic) or 104 (negative logic)" in any of
Pr. 190 to Pr. 192.
All signals are off during DC injection brake.
The output frequency to be compared with the set frequency is the output frequency before
slip compensation is performed.
Changing the terminal assignment using Pr.190 to Pr.192 "Output terminal function selec-
tion" may affect the other functions. Make setting after confirming the function of each termi-
nal.
6 - 130
Forward
rotation
ON
FU
Time
Reverse
rotation
ON
Parameter
I001798E