Mitsubishi Electric FR-E700 Instruction Manual page 180

Frequency inverter
Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Adjust the output torque (current) of the motor
Selection method of general-purpose magnetic flux vector control
Motor
Mitsubishi standard
motor
Mitsubishi high effi-
ciency motor
Mitsubishi constant-
torque motor
Other manufacturer's
standard motor
Other manufacturer's
constant-torque motor
Perform offline auto tuning. (Pr. 96) (Refer to section 6.8.3.)
Set slip compensation. (Pr. 245, Pr. 246, Pr. 247) (Refer to section 6.3.4.)
Fig. 6-4: Selection method of general-purpose magnetic flux vector control
NOTES
Uneven rotation slightly increases as compared to the V/f control. It is not suitable for
machines such as grinding machine and wrapping machine which requires less uneven
rotation at low speed.
When a surge voltage suppression filter (FFR-DT) is connected between the inverter and
motor, output torque may decrease.
6 - 40
Perform secure wiring.
(Refer to section 3.2.)
Set the motor. (Pr. 71)
SF-JR
SF-HR
Others
SF-JRCA 4P
SF-HRCA 4P
Others (SF-JRC, etc.)
Refer to section 6.8.2, for other settings of Pr. 71.
Refer to section 6.8.3 for offline auto tuning.
Set the motor capacity and the number of motor poles.
(Pr. 80, Pr. 81) (Refer to section 6.2.1.)
Select the control method. (Pr. 800)
(Refer to section 6.3.2.)
Set the operation command.
(Refer to section 6.18.1.)
Test run
Pr. 71
0
(initial value)
40
3
1
50
13
3
13
Set motor capacity (kW) in Pr. 80 "Motor capacity" and the number of
motor poles (number of poles) in Pr. 81 "Number of motor poles".
(V/f control is performed when the setting is "9999" (initial value).
Set "30" (initial value) in Pr. 800 to make general-purpose magnetic flux
vector control valid.
Select the start command and speed command.
1) Start command
– Operation panel: Setting by pressing the RUN key of the
operation panel
– External command: Setting by forward rotation or reverse
rotation command (terminal STF or STR)
2) Speed command
– Operation panel: Setting by pressing the digital dial of the
operation panel
– External analog command (terminal 2 or 4):
Give a speed command using the analog signal input to
terminal 2 (or terminal 4).
– Multi-speed command:
The external signals (RH, RM, RL) may also be used to give
speed command.
Parameter
Remarks
Offline auto tuning is necessary
Offline auto tuning is necessary
Offline auto tuning is necessary
Offline auto tuning is necessary