External operation
5.3.2
Use switches to give a start command and a frequency command (multi-
speed setting) (Pr. 4 to Pr. 6)
● Start command by terminal STF (STR)-PC.
● Frequency command by terminal RH, RM, RL and STR-PC.
● "EXT" must be lit. (When "PU" is lit, switch it to "EXT" with the PU/EXT key.)
● The initial values of the terminals RH, RM, RL are 50Hz, 30Hz, and 10Hz. (Use Pr. 4, Pr. 5
and Pr. 6 to change.)
● Operation at 15-speed can be performed by turning two (or three) terminals simultaneously.
(Refer to section 6.6.1.)
Fig. 5-23: Frequency and start command by switches
RH
RM
RL
Fig. 5-24: Multi-speed selection by external terminals