Use Switches To Give A Start Command And A Frequency Command (Multi-Speed Setting) (Pr. 4 To Pr. 6) - Mitsubishi Electric FR-E700 Instruction Manual

Frequency inverter
Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

External operation
5.3.2
Use switches to give a start command and a frequency command (multi-
speed setting) (Pr. 4 to Pr. 6)
● Start command by terminal STF (STR)-PC.
● Frequency command by terminal RH, RM, RL and STR-PC.
● "EXT" must be lit. (When "PU" is lit, switch it to "EXT" with the PU/EXT key.)
● The initial values of the terminals RH, RM, RL are 50Hz, 30Hz, and 10Hz. (Use Pr. 4, Pr. 5
and Pr. 6 to change.)
● Operation at 15-speed can be performed by turning two (or three) terminals simultaneously.
(Refer to section 6.6.1.)
Fig. 5-23: Frequency and start command by switches
RH
RM
RL
Fig. 5-24: Multi-speed selection by external terminals
5 - 32
Power supply
Forward rotation start
Reverse rotation start
High speed
Middle speed
Low speed
Speed 1 (high speed)
Speed 2
(middle speed)
Speed 3
(low speed)
ON
ON
ON
Inverter
Motor
Speed 5
Speed 6
Speed 4
ON
ON
ON
ON
ON
Basic settings
I0001086E
Speed 7
t
ON
ON
ON
I000004aC

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e720sFr-e740Fr-e700 seriesFr-e720s ecFr-e740 ec

Table of Contents