Parameter
PU operation mode (Pr. 79 = 1)
Select the PU operation mode when applying start and speed command by only the key oper-
ation of the operation panel (FR-PU04/FR-PU07). Also select the PU operation mode when
making communication using the PU connector.
When "1" is selected for Pr. 79, the inverter enters the PU operation mode at power on. You can-
not change to the other operation mode.
The setting dial of the operation panel can be used for setting like a volume. (Pr. 161 "Frequency
setting/key lock operation selection", refer to section 6.22.3).
When PU operation mode is selected, the PU operation mode signal (PU) can be output. For the
terminal used for the PU signal output, assign the function by setting "10 (source logic) or 110
(sink logic)" in any of Pr. 190 to Pr. 192 "Output terminal function selection".
supply
FR-E700 EC
Inverter
Power
Operation
panel
Selection of operation mode and operation location
Fig. 6-105:
PU operation mode
Motor
I001825E
6 - 203