Function assignment of external terminals
NOTES
Changing the terminal assignment using Pr. 178 to Pr. 184 "Input terminal function
selection" may affect the other functions. Please make setting after confirming the function of
each terminal.
One function can be assigned to two or more terminals. In this case, the terminal inputs are
ORed.
The priorities of the speed commands are in order of jog, multi-speed setting (RH, RM, RL,
REX) and PID (X14).
When the X10 signal (FR-HC, FR-CV connection - inverter operation enable signal) is not
set, the MRS signal shares this function.
When the PU operation external interlock (X12) signal is not assigned at the Pr. 79 "Opera-
tion mode selection" setting of "7", the MRS signal shares this function.
Use common terminals to assign multi-speeds (7 speeds) and remote setting. They cannot
be set individually. (Common terminals are used since these functions are designed for
speed setting and need not be set at the same time.)
When V/f control is selected by V/f switchover (X18 signal), second function is also selected
at the same time. Control between V/f and advanced (general-purpose) magnetic flux can
not be switched during operation. In case control is switched between V/f and advanced
(general-purpose) magnetic flux, only second function is selected.
Turning the AU signal on makes terminal 2 (voltage input) invalid.
Response time of each signal
The response time of the X10 signal and MRS signal is within 2ms.
The response time of other signals is within 20ms.
6 - 116
Parameter