Common Specifications; Fr-E720S-008; A.2 Common Specifications - Mitsubishi Electric FR-E700 Instruction Manual

Frequency inverter
Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Appendix
A.2

Common specifications

FR-E740
Control system
Modulation control
Output frequency range
Analog input
Frequency setting
resolution
Digital input
Analog input
Frequency accuracy
Digital input
Voltage/frequency characteristics
Starting torque
Torque boost
Acceleration/deceleration time
Acceleration/deceleration characteristics
Regenerative
Braking torque
DC injection brake
Stall prevention
Analog input
Frequency setting
values
Digital input
Start signal
Input signals
Operational functions
Open collector out-
puts
Relay outputs
Operating status
Output signals
Analog output
For meter
Tab. A-3: Common specifications (1)
FR-E700 EC
V/f control, optimum excitation control, general-purpose magnetic flux vector control or advanced
magnetic flux vector control can be selected
0.06Hz/0–50Hz (terminal 2, 4: 0–10V/10bit)
0.12Hz/0–50Hz (terminal 2, 4: 0–5V/9bit)
0.06Hz/0–50Hz (terminal 4: 0/4–20mA/10bit)
±0.5% of the maximum output frequency (temperature range 25°C ±10°C)
±0.01% of the set output frequency
Base frequency can be set from 0 to 400Hz
Constant torque/variable torque pattern can be selected
200% or more (at 0.5Hz) ... when advanced magnetic flux vector control is set (3.7K or less)
0.01 to 360s; 0.1 to 3600s (can be set individually)
Linear or S-form course, user selectable
FR-E720S-008 and 015 ... 150 %,
FR-E720S-030 and 050, FR-E740-016 and 026 ... 100 %,
FR-E720S-080, FR-E740-040 ... 50%,
FR-E720S-0110, FR-E740-060 or more... 20%
Operation frequency (0 to 120Hz), operation time (0 to 10s)
and operation voltage (0 to 30%) can be set individually.
Responses threshold 0–200%, user adjustable
Terminal 4: 0–5V DC, 0–10V DC, 0/4–20mA
Entered from operation panel and parameter unit
Forward and reverse rotation or start signal automatic
self-holding input (3-wire input) can be selected.
Any of 7 signals can be selected using parameters 178 to 184 "Input terminal function selection":
multi-speed selection, remote setting, stop-on contact selection, second function selection, termi-
nal 4 input selection, JOG operation selection, PID control valid terminal, brake opening comple-
tion signal, external thermal input, PU-external operation switchover, V/f switchover, output stop,
start self-holding selection, forward rotation, reverse rotation command, inverter reset, PU-NET
operation switchover, external-NET operation switchover, command source switchover, inverter
operation enable signal, and PU operation external interlock
Maximum/minimum frequency setting, frequency jump operation, external thermal relay input
selection, automatic restart after instantaneous power failure operation, forward/reverse rotation
prevention, remote setting, brake sequence, second function, multi-speed operation, stop-on
contact control, droop control, regeneration avoidance, slip compensation, operation mode selec-
tion, offline auto tuning function, PID control, computer link operation (RS-485)
Selection can be made from inverter operation, up-to-frequency, overload alarm, output fre-
quency detection, regenerative brake prealarm, electronic thermal relay function prealarm, inver-
ter operation ready, output current detection, zero current detection, PID lower limit, PID upper
limit, PID forward/reverse rotation output, brake opening request, fan alarm (FR-E720S-050 or
more, FR-E740-040 or more), heatsink overheat pre-alarm, deceleration at an instantaneous
power failure, PID control activated, during retry, life alarm, current average value monitor,
remote output, alarm output, fault output, fault output 3, and maintenance timer alarm using
Pr. 190 to Pr. 192 "Output terminal function selection".
Selection can be made from output frequency, motor current (steady), output voltage, frequency
setting, motor torque, converter output voltage, regenerative brake duty, electronic thermal relay
function load factor, output current peak value, converter output voltage peak value, reference
voltage output, motor load factor, PID set point, PID measured value, output power 0 to 10VDC
using Pr. 158 "AM terminal function selection".
Specification
Sine evaluated PWM, Soft PWM
0.2–400Hz
0.01Hz
Manual torque boost
Terminal 2: 0–5V DC, 0–10V DC
2 points
1 point
0–10V DC: 1 point
Common specifications
A - 3