Mitsubishi Electric FR-E700 Instruction Manual page 382

Frequency inverter
Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Communication operation and setting
Fig. 6-126: General flowchart
NOTES
Always set the communication check time interval before starting operation to prevent haz-
ardous conditions.
Data communication is not started automatically but is made only once when the computer
provides a communication request. If communication is disabled during operation due to sig-
nal cable breakage etc., the inverter cannot be stopped. When the communication check
time interval has elapsed, the inverter will come to an alarm stop (E.PUE). The inverter can
be coasted to a stop by switching on its RES signal or by switching power off.
If communication is broken due to signal cable breakage, computer fault etc., the inverter
does not detect such a fault. This should be fully noted.
6 - 242
Port open
Communication setting
Time out setting
Send data processing
Data setting
Sum code calculation
Data transmission
Receive data waiting
Receive data
processing
Data retrieval
Screen display
Parameter

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e720sFr-e740Fr-e700 seriesFr-e720s ecFr-e740 ec

Table of Contents