Mitsubishi Electric FR-E700 Instruction Manual page 265

Frequency inverter
Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Parameter
Setting
Terminal Function
Source
Sink
Logic
Logic
11
111
RY
12
112
Y12
13
113
Y13
14
114
FDN
15
115
FUP
16
116
RL
20
120
BOF
25
125
FAN
26
126
FIN
46
146
Y46
47
147
PID
64
164
Y64
Tab. 6-31:
Output terminal function assignment (2)
FR-E700 EC
Inverter operation ready
Output current detection
Zero current detection
PID lower limit
PID upper limit
PID forward/reverse rotation
output
Brake opening request
Fan fault output
Heatsink overheat prealarm
During deceleration at occur-
rence of power failure (retained
until release)
During PID control activated
During retry
Function assignment of external terminals
Operation
Output when the inverter can
be started by switching the
start signal on or while it is
running.
Output when the output cur-
rent is higher than the Pr. 150
setting for longer than the
time set in Pr. 151.
Output when the output
power is lower than the
Pr. 152 setting for longer than
the time set in Pr. 153.
Output when the feedback
value falls below the lower
limit of PID control.
Output when the feedback
value rises above the upper
limit of PID control.
Output when forward rotation
is performed in PID control.
Output to open the brake
when the brake sequence
function is selected.
Output at the time of a fan
fault.
Output when the heatsink
temperature reaches about
85% of the heatsink overheat
protection providing tempera-
ture.
Output when the power fail-
ure-time deceleration function
is executed.
Output during PID control.
Output during retry
processing.
Related Parame-
Refer to
ters
Page
6-127
Pr. 150, Pr. 151
6-131
Pr. 152, Pr. 153
6-131
Pr. 127–Pr. 134
6-270
Pr. 278–Pr. 283,
6-109
Pr. 292
Pr. 244
6-295
7-11
Pr. 261
6-162
Pr. 127–Pr. 134
6-270
Pr. 65–Pr. 69
6-166
6 - 125