Advertisement

Frequency setting by analog input (terminal 2, 4)

6.16
Frequency setting by analog input (terminal 2, 4)
Purpose
Selection of voltage/current input
(terminal 2, 4)
Perform forward/reverse rotation by
analog input.
Adjustment (calibration) of analog
input frequency and voltage (cur-
rent)
6.16.1

Analog input selection (Pr. 73, Pr. 267)

You can select the function that switches between forward rotation and reverse rotation
according to the analog input terminal specifications and input signal.
The following settings are possible:
● Select reference voltages and currents:: 0–10V, 0–5V oder 0/4–20mA
● Suppress motor reversing
Pr.
Initial
Name
No.
Value
Analog input
73
1
selection
Terminal 4
267
0
input selection
The above parameters can be set when Pr. 160 "User group read selection" = 0.
6 - 174
Parameters that must be set
Analog input selection
Bias and gain of frequency setting volt-
age (current)
Setting
Description
Range
0
Terminal 2: 0–10V
1
Terminal 2: 0–5V
10
Terminal 2: 0–10V
11
Terminal 2: 0–5V
Voltage/current input switch Description
0
1
2
Pr. 73, Pr. 267
Pr. 125, Pr. 126,
Pr. 241, C2–C7
(Pr. 902–Pr. 905)
Parameters referred to
Without reversible
operation
With reversible
operation
Terminal 4: 0/4–20mA
Terminal 4: 0–5V
Terminal 4: 0–10V
Parameter
Refer to
Section
6.16.1
6.16.3
Refer to
Section
125
Terminal 2
6.16.3
frequency setting
gain frequency
126
Terminal 4
6.16.3
frequency setting
gain frequency
C2
Terminal 2 fre-
6.16.3
quency setting
bias frequency
to
6.16.3
C7
Terminal 4 fre-
quency setting
gain