Wiring Methods
CS-series 96-point I/O
Units
Wire Sizes

Wiring Procedure

1,2,3...
The following connectors are recommended for attachment to CS-series 96-
point I/O Units.
Connection
Solder-type
(included with Unit)
Crimp-type
Crimp-type
Note Solder-type connectors are included with each Unit.
We recommend using cable with wire gauges of AWG 28 to AWG 26
2
(0.2 mm
to 0.13 mm
max.
1. Check that each Unit is installed securely.
Note Do not apply excessive force on the cables.
2. Do not remove the protective label from the top of the Unit until wiring has
been completed. This label prevents wire strands and other foreign matter
from entering the Unit during wiring. (Remove the label after wiring has
been completed to allow air circulation needed for cooling.)
Before wiring
3. When solder-type connectors are being used, be sure not to accidentally
short adjacent terminals. Cover the solder joint with heat-shrink tubing.
Pins
OMRON set
56
CS1W-CE561
Socket: FCN-361J056-AU
Connector bar: FCN-360C056-J3
56
CS1W-CE562
Socket: FCN-363J056
Connector bar: FCN-360C056-J3
Contacts: FCN-363J-AU
56
CS1W-CE563
FCN-367J056-AU/F
2
). Use cable with external wire diameters of 1.61 mm
After wiring
Section 5-4
Fujitsu parts
Remove label
after wiring
177