Omron CS1D DUPLEX SYSTEM - 10-2009 Operation Manual page 605

Cs1d duplex system
Table of Contents

Advertisement

Precautions in Replacing CS1-H PLCs with CS1D PLCs
Item
Instruc-
PRV2 instruction
tions
TXDU and RXDU
and
instructions
tasks,
Model conversion
contd
instructions:
XFERC, DISTC,
COLLC, MOVBC,
and BCNT
Special function
block instruction:
GETID
PLC Setup
Pro-
CX-Programmer
gram-
restrictions
ming
Devices
Device type setting CX-Programmer Version 3.@
Connecting to PLC The Programming Device
Duplex CPU Systems
Not supported.
Not supported.
Not supported.
Not supported.
If CS1 or CS1-H PLC Setups
are used, the CS1D will
change any setting that it
does not support (e.g., inter-
rupt settings for the CPU Unit,
CPU execution modes for
peripheral servicing, etc.)
Supported from CX-Program-
mer version 3.1.
Supported from CX-Program-
mer version 2.1 or lower with
the following restrictions.
Version 2.1: Duplex error dis-
plays, PLC Setup settings,
and online Unit replacement
are not supported.
Version 3.0: Online Unit
replacement are not sup-
ported.
or Lower
Select "CS1H-H" as the
device type. When using
duplex functions, select
Duplex Settings from the
Option Menu in the PLC
Setup. Duplex operation must
be set in the PLC Setup.
CX-Programmer Version 4.0
or Higher
Select "CS1D-H" as the
device type when using a
Duplex CPU System. The
"CS1H-H" can also be
selected as the device type,
but if it is, then Duplex Set-
tings must be selected from
the Option Menu in the PLC
Setup. Duplex operation must
be set in the PLC Setup.
must be connected to the
active CPU Unit; it will not be
possible to transfer data or
otherwise write data when
connected to the standby
CPU Unit.
Single CPU Systems
Not supported.
Not supported.
Not supported.
Not supported.
All settings in the PLC Setup for the
CS1-H can be used.
(No precautions in converting from
the CS1-H.)
Supported from CX-Programmer
version 4.0. CX-Programmer Version
3.@ or lower cannot be used.
Select "CS1D-S" as the device type.
Online connection will not be possi-
ble if "CS1D-H" is selected.
Duplex operation must be set in the
PLC Setup.
---
Appendix E
CS1-H (See note.)
Supported.
Supported.
Supported.
Supported.
---
Supported from CX-
Programmer ver-
sion 2.1.
Select "CS1H-H" as
the device type.
---
569