General Specifications - Omron CS1D DUPLEX SYSTEM - 10-2009 Operation Manual

Cs1d duplex system
Table of Contents

Advertisement

Specifications
2-1-4

General Specifications

Item
CS1D Power Supply Unit
Power supply voltage
Operating voltage range
Power consumption
Inrush current
Power supply output capacity
Power supply output terminal
RUN output
Contact configu-
(See note 3.)
ration
Switch capacity
Insulation resistance
Dielectric strength
Noise immunity
Vibration resistance
Shock resistance
Ambient operating temperature
Ambient operating humidity
Atmosphere
Ambient storage temperature
Grounding
Enclosure
CS1D-PA207R
100 to 120 V AC/200 to
240 V, 50/60 Hz
85 to 132 V AC/170 to
264 V
150 VA max.
100 to 120 V AC: 30 A
max. (cold start at normal
temperatures); 8 ms max.
200 to 240 V AC: 40 A
max. (cold start at normal
temperatures); 8 ms max.
(See note 1.)
5 V DC, 7 A (including the
CPU Unit power supply)
26 V DC, 1.3 A
Total: 35 W max.
Not provided.
SPST-NO
240 V AC, 2A (resistive
load)
120 V AC, 0.5 A (induction
load)
24 V DC, 2A (resistive
load)
24 V DC, 2 A (induction
load)
20 M min. (at 500 V DC)
between AC external and
GR terminals (See note 2.)
2,300 V AC 50/60 Hz for 1
min between AC external
and GR terminals (See
note 2.)
Leakage current: 10 mA
max.
1,000 V AC 50/60 Hz for 1
min between AC external
and GR terminals (See
note 2.)
Leakage current: 10 mA
max.
2 kV on power supply line (conforming to IEC61000-4-4)
10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s
directions for 80 minutes
(Time coefficient: 8 minutes
2
147 m/s
3 times each in X, Y, and Z directions (according to JIS 0041)
0 to 55 C
10% to 90% (with no condensation)
Must be free from corrosive gases.
20 to 75 C (excluding battery)
Less than 100
Mounted in a panel.
Specifications
CS1D-PD024
24 V DC
19.2 to 28.8 V DC
40 W max.
30 A max.
5 V DC, 4.3 A (including the
CPU Unit power supply)
26 V DC, 0.56 A
Total: 28 W max.
Not provided.
Not provided.
20 M min. (at 500 V DC)
between DC external and
GR terminals (See note 2.)
1,000 V AC 50/60 Hz for 1
min between DC external
and GR terminals (See note
2.)
Leakage current: 10 mA
max.
coefficient factor 10 = total time 80 min.)
Section 2-1
CS1D-PD025
24 V DC
19.2 to 28.8 V DC
60 W max.
30 A max.
5 V DC, 5.3 A (including the
CPU Unit power supply)
26 V DC, 1.3 A
Total: 40 W max.
Not provided.
Not provided.
20 M min. (at 500 V DC)
between DC external and
GR terminals (See note 2.)
1,000 V AC 50/60 Hz for 1
min between DC external
and GR terminals (See note
2.)
Leakage current: 10 mA
max.
2
in X, Y, and Z
29

Advertisement

Table of Contents
loading

Table of Contents