Omron CS1D DUPLEX SYSTEM - 10-2009 Operation Manual page 553

Cs1d duplex system
Table of Contents

Advertisement

Auxiliary Area Allocations
Address
Name
Words
Bits
A320
Error Power Supply Unit Location
When the voltage on the primary side of the Power Supply Unit drops or is interrupted, one of the following bits will turn ON to
show the location of the Power Supply Unit with the error. A31602 (Duplex Power Supply Unit Error Flag) can be used to deter-
mine if there is an error and the following bits can be used to locate the error.
A32000
Right Power Supply Unit on CPU Rack (Rack 0)
A32001
Left Power Supply Unit on CPU Rack (Rack 0)
A32002
Right Power Supply Unit on CPU Rack (Rack 1)
A32003
Left Power Supply Unit on CPU Rack (Rack 1)
A32004
Right Power Supply Unit on CPU Rack (Rack 2)
A32005
Left Power Supply Unit on CPU Rack (Rack 2)
A32006
Right Power Supply Unit on CPU Rack (Rack 3)
A32007
Left Power Supply Unit on CPU Rack (Rack 3)
A32008
Right Power Supply Unit on CPU Rack (Rack 4)
A32009
Left Power Supply Unit on CPU Rack (Rack 4)
A32010
Right Power Supply Unit on CPU Rack (Rack 5)
A32011
Left Power Supply Unit on CPU Rack (Rack 5)
A32012
Right Power Supply Unit on CPU Rack (Rack 6)
A32013
Left Power Supply Unit on CPU Rack (Rack 6)
A32014
Right Power Supply Unit on CPU Rack (Rack 7)
A32015
Left Power Supply Unit on CPU Rack (Rack 7)
A322
CPU Standby Information
A32203
CPU Bus/
Special I/O
Unit Star-
tup Flag
A32204
Duplex
Bus Error
Standby
Flag
A32205
Duplex
Verifica-
tion Error
Standby
Flag
A32206
Waiting for
Other CPU
Unit
Standby
Flag
A32207
Inner
Board
Startup
Flag
A32208
Expan-
sion Power
OFF
Standby
Flag
A324
A32406
Inner
Board
Error
A32407
Flags
(Non-fatal
error)
(Duplex
CPU Sys-
tem only)
A32411
Right/Left
CPU Unit
Battery
A32413
Error
Flags
(Duplex
CPU Sys-
tem only)
Function
ON: The CPU Unit is on standby
waiting for CPU Bus or Special I/O
Units to start.
ON: The CPU Unit is on standby
because a duplex bus error occurred
at startup. (Duplex CPU System
only)
ON: The CPU Unit is on standby
because a duplex verification error
occurred at startup. (Duplex CPU
System only)
ON: The CPU Unit is on standby
waiting for the other CPU Unit to
start operation at startup. (Duplex
CPU System only)
ON: The CPU Unit is on standby
waiting for an Inner Board to start.
(Single CPU Systems or Process-
control CPU Units only)
ON: The CPU Unit is on standby
because power is not being supplied
to an Expansion Rack.
ON if A40208 turns ON for the right
Inner Board.
ON if A40208 turns ON for the left
Inner Board.
ON if A40204 is ON in the right CPU
Unit.
ON if A40204 is ON in the left CPU
Unit.
Settings
Status
after
mode
change
ON: Primary-
Cleared
side input power
error
OFF: Normal
ON: Standby
Held
OFF: Other
ON: Non-fatal
Cleared
Inner Board
Error
OFF: Normal
ON: Battery
Cleared
error
OFF: Normal
Appendix B
Status at
Timing
Related
startup
flags,
settings
Cleared
When
A31602
error
occurs
Cleared
When
---
CPU Unit
goes on
standby
Cleared
When
A402
error
occurs
Cleared
When
A402
error
occurs
A402
517

Advertisement

Table of Contents
loading

Table of Contents