Omron CS1D DUPLEX SYSTEM - 10-2009 Operation Manual page 508

Cs1d duplex system
Table of Contents

Advertisement

Specifications of Basic I/O Units and High-density I/O Units
Basic Output Units
CS1W-OC211 Contact Output Unit (16 points)
Max. Switching Capacity
Min. Switching Capacity
Relay Replacement
Service Life of Relay
ON Response Time
OFF Response Time
No. of Circuits
Number of Inputs ON Simulta-
neously
Surge Protector
Fuses
Insulation Resistance
Dielectric Strength
Internal Current Consumption 130 mA 5 V DC max. 96 mA 26 V DC (6 mA
Weight
Circuit Configuration
Terminal Connections
Note Terminal numbers A0 to A9 and B0 to B9 are used in this manual, but they are not printed on the Unit.
472
2 A 250 V AC (cos = 1), 2 A 24 V DC (8 A/common, 16 A/Unit), 0.1 A 120 V DC
1 mA 5 V DC
NY-24W-K-IE (Fujitsu Takamizawa Component Ltd.)
Relays cannot be replaced by users.
Electrical: 150,000 operations (resistive load)/100,000 operations (inductive load)
Mechanical: 20,000,000 operations
Service life will vary depending on the connected load. Refer to page 497 for information
on service life according to the load.
15 ms max.
15 ms max.
16 points (8 points/common, 2 commons)
16
None
None
20 M between external terminals and the GR terminal (500 V DC)
2,000 V AC between the external terminals and the GR terminal for 1 minute at a leakage
current of 10 mA max.
290 g max.
Output indicator
2 A 250 VAC,
2 A 24 VDC,
0.1 A 120 VDC max.
No. points ON)
OUT0
to
OUT7
COM0
OUT8
to
OUT15
COM1
0
L
A0
1
2
B0
L
L
A1
3
4
B1
L
L
A2
5
6
B2
L
L
A3
7
B3
L
COM0
A4
NC
8
B4
L
A5
9
10
B5
L
L
A6
11
12
B6
L
L
A7
13
14
B7
L
L
A8
15
B8
L
COM1
A9
NC
B9
Appendix A

Advertisement

Table of Contents
loading