Auxiliary Area Allocations
Address
Name
Words
Bits
A402
A40215
FAL Error
Flag
(Non-fatal
error)
A403
A40300
Memory
to
Error
A40308
Location
A40309
Memory
Card
Start-up
Transfer
Error Flag
A40310
Flash
Memory
Error
A404
A40400
I/O Bus
to
Error Slot
A40407
Number
A40408
I/O Bus
to
Error Rack
A40415
Number
A405
A40515
Peripheral
Servicing
Too Long
Flag (Sin-
gle CPU
Systems
onl7)
Function
ON when a non-fatal error is gener-
ated by executing FAL(006). The
CPU Unit will continue operating and
the ERR/ALM indicator on the front
of the CPU Unit will flash.
The bit in A360 to A391 that corre-
sponds to the FAL number specified
in FALS(006) will be turned ON and
the corresponding error code will be
written to A400. Error codes 4101 to
42FF correspond to FAL numbers
001 to 2FF (0 to 511).
(This flag will be turned OFF when
the error is cleared.)
When a memory error occurs, the
Memory Error Flag (A40115) is
turned ON and one of the following
flags is turned ON to indicate the
memory area where the error
occurred.
A40300: User program
A40304: PLC Setup
A40305: Registered I/O Table
A40307: Routing Table
A40308: CPU Bus Unit Settings
When a memory error occurs, the
CPU Unit will continue operating and
the ERR/ALM indicator on the front
of the CPU Unit will flash.
(The corresponding flag will be
turned OFF when the error is
cleared.)
ON when automatic transfer at start-
up has been selected and an error
occurs during automatic transfer. An
error will occur if there is a transfer
error, the specified file does not
exist, or the Memory Card is not
installed.
(This flag will be turned OFF when
the error is cleared by turning the
power off. The error cannot be
cleared without turning the power
off.)
Turns ON when the flash memory
fails.
Contains the 8-bit binary slot num-
ber (00 to 08) where an I/O Bus
Error occurred.
CPU Unit operation will stop and the
ERR/ALM indicator on the front of
the CPU Unit will light. The I/O Bus
Error Flag (A40114) will be ON.
(This flag will be turned OFF when
the error is cleared.)
Contains the 8-bit binary rack num-
ber (00 to 07) where an I/O Bus
Error occurred.
CPU Unit operation will stop and the
ERR/ALM indicator on the front of
the CPU Unit will light. The I/O Bus
Error Flag (A40114) will be ON.
(This flag will be turned OFF when
the error is cleared.)
Turns ON when the peripheral ser-
vicing time in a Parallel Processing
Mode exceeds 2 s. This will also
cause a cycle time error and opera-
tion will stop.
Settings
Status
after
mode
change
ON: FALS(006)
Cleared
error occurred
OFF: FALS(006)
not executed
ON: Error
Cleared
OFF: No error
ON: Error
Cleared
OFF: No error
ON: Error
Clear
OFF: No error
00 to 08 hex
Cleared
(slot No. 0 to 8)
00 to 03 hex
Cleared
(Rack No. 0 to 3)
1: Too long (Par-
Cleared
allel processing
cannot be used.)
0: Not too long
(Parallel pro-
cessing can be
used.)
Appendix B
Status at
Timing
Related
startup
flags,
settings
Cleared
When
A360 to
error
A391,
occurs
A400
Cleared
---
A40115
Cleared
When
---
power is
turned ON
Clear
When
error
occurs
Cleared
---
A40114
Cleared
---
A40114
Cleared
Written
A268
when
error
occurs
531