PC Link Unit Replacement Procedure

3-2

PC Link Unit Replacement Procedure

Item
Unit or setting
CPU Rack
CPU Unit (C500, C1000H, or
replacement
C2000H)
CPU Backplane
Power Supply Unit
I/O Units
Special I/O Units
SYSMAC LINK Units
Host Link Units
PC Link Units
PC Link Unit
CPU Bus Unit unit number
settings
setting
Node address setting
Number of LR bits setting
Operating level/Link number
setting
Transmission line setting (two-
wire or four-wire method)
Terminating resistance
Number of I/O points to
refresh
Single/Double Unit allocation
Precautions
LR Area words used in PC
when writing
Link
ladder program
PLC Run and PC Link Error
Flags
Level Flags
CPU Bus Unit status area
PLC CPU Unit
Setting the PLC's operation
settings
mode (synchronous/asyn-
chronous operation)
34
The following table outlines the procedures and precautions for replacement
of PC Link Units.
Replace with CVM1/CV-series compo-
nents.
Some can be used in the CVM1/CV
Series.
Replace with CVM1/CV-series compo-
nents.
Replace with CVM1-LK401.
The unit number must be set since the
CVM1-LK401 is a CPU Bus Unit.
Match the CVM1-LK401's settings to
the settings of the C500-LK009-V1
Units in the PC Link.
(One exception is the LK003 mode,
which cannot be used. In this case,
change the C500-LK009-V1 Units'
settings.)
These settings are not set in the
CVM1-LK401.
Replace LR 00 to LR 63 addresses
with CIO 1000 to CIO 1063.
Replace SR 247 to SR 250 bit
addresses with CIO 1500 + 25 × N to
CIO 1500 + 25 × N +3 (N = unit num-
ber).
Replace AR 2411 and AR 2412 bit
addresses with bits 11 and 12 of CIO
1500 + 25 × N +4 (N = unit number).
In the CVM1/CV Series, the status of
the CVM1-LK401 can be monitored
from the ladder program.
We recommend using synchronous
operation.
Description
Section 3-2
Reference
CV-Series Programmable
Controllers Installation Guide
(W195-E1-5)
3-3 CVM1-LK401 Switch Set-
tings
3-3-1 Setting the Unit Number
3-3-2 Setting the Node
Address in the PC Link
3-3-3 Setting the Number of
LR Bits (Max. Number of PC
Link Units)
3-3-4 Setting the Level/Link
Number
3-3-5 Setting the Transmis-
sion Line and Terminating
Resistance
---
3-4-1 LR Area
3-4-2 PC Link Status Area
3-4-3 Level Flags
3-4-4 CPU Bus Unit Status
Flags
3-5 PLC Operation Mode
(Synchronous/Asynchronous
Mode)