Auxiliary Area Allocations
Address
Name
Words
Bits
A402
A40202
Special I/O
Unit Set-
ting Error
Flag
(Non-fatal
error)
A40203
CPU Bus
Unit Set-
ting Error
Flag
(Non-fatal
error)
A40204
Battery
Error Flag
(Non-fatal
error)
A40206
Special I/O
Unit Error
Flag
(Non-fatal
error)
A40207
CPU Bus
Unit Error
Flag
(Non-fatal
error)
Function
ON when an installed Special I/O
Unit does not match the Special I/O
Unit registered in the I/O table. The
CPU Unit will continue operating and
the ERR/ALM indicator on the front
of the CPU Unit will flash.
The unit number of the Unit where
the setting error occurred is indi-
cated in A428 to A433.
(This flag will be turned OFF when
the error is cleared.)
ON when an installed CPU Bus Unit
does not match the CPU Bus Unit
registered in the I/O table. The CPU
Unit will continue operating and the
ERR/ALM indicator on the front of
the CPU Unit will flash.
The unit number of the Unit where
the setting error occurred is written
to A427.
(This flag will be turned OFF when
the error is cleared.)
ON if the CPU Unit's battery is dis-
connected or its voltage is low and
the Detect Battery Error setting has
been set in the PLC Setup.
With a Duplex CPU System, this flag
applies to both the left and right
CPU Unit.
The CPU Unit will continue operat-
ing and the ERR/ALM indicator on
the front of the CPU Unit will flash.
This flag can be used to control an
external warning light or other indi-
cator to indicate that the battery
needs to be replaced.
(This flag will be turned OFF when
the error is cleared.)
ON when an error occurs in a data
exchange between the CPU Unit
and a Special I/O Unit (including an
error in the Special I/O Unit itself).
The CPU Unit will continue operat-
ing and the ERR/ALM indicator on
the front of the CPU Unit will flash.
The Special I/O Unit where the error
occurred will stop operating and the
unit number of the Unit where the
data exchange error occurred is indi-
cated in A418 through A423.
(This flag will be turned OFF when
the error is cleared.)
ON when an error occurs in a data
exchange between the CPU Unit
and an CPU Bus Unit (including an
error in the CPU Bus Unit itself).
The CPU Unit will continue operat-
ing and the ERR/ALM indicator on
the front of the CPU Unit will flash.
The CPU Bus Unit where the error
occurred will stop operating and the
unit number of the Unit where the
data exchange error occurred is indi-
cated in A417.
(This flag will be turned OFF when
the error is cleared.)
Settings
Status
after
mode
change
ON: Setting error
Cleared
detected
OFF: No setting
error
ON: Setting error
Cleared
detected
OFF: No setting
error
ON: Error
Cleared
OFF: No error
ON: Error in one
Cleared
or more Units
OFF: No errors
in any Unit
ON: Error in one
Cleared
or more Units
OFF: No error in
any Unit
Appendix B
Status at
Timing
Related
startup
flags,
settings
Cleared
---
A428 to
A433
Cleared
---
A427
Cleared
---
PLC
Setup
(Detect
Battery
Error)
A324
Cleared
---
A418 to
A423
Cleared
---
A417
529