Auxiliary Area Allocations
Address
Name
Words
Bits
A317
Duplex Verification Errors (Duplex CPU Systems only)
(When A31600 turns ON, the cause of the error will be indicated here.)
A31706
Other CPU
Unit
Duplex
Verifica-
tion Error
Flag
(Duplex
CPU Sys-
tem only)
A31707
CPU Unit
Model Ver-
ification
Error Flag
A31708
CPU Unit
Version
Verifica-
tion Error
Flag
A31710
Inner
Board
Model Ver-
ification
Error Flag
A31713
Parameter
Area Veri-
fication
Error Flag
A31714
No Active
CPU Unit
Error Flag
(Duplex
CPU Sys-
tem only)
A31715
User Pro-
gram Veri-
fication
Error Flag
A319
Error Power Supply Unit Location
When an error in a Power Supply Unit results in an error in the 5-V/26-V output, one of the following bits will turn ON to show
the location of the Power Supply Unit with the error. A31602 (Duplex Power Supply Unit Error Flag) can be used to determine
if there is an error and the following bits can be used to locate the error.
A31900
Right Power Supply Unit on CPU Rack (Rack 0)
A31901
Left Power Supply Unit on CPU Rack (Rack 0)
A31902
Right Power Supply Unit on CPU Rack (Rack 1)
A31903
Left Power Supply Unit on CPU Rack (Rack 1)
A31904
Right Power Supply Unit on CPU Rack (Rack 2)
A31905
Left Power Supply Unit on CPU Rack (Rack 2)
A31906
Right Power Supply Unit on CPU Rack (Rack 3)
A31907
Left Power Supply Unit on CPU Rack (Rack 3)
A31908
Right Power Supply Unit on CPU Rack (Rack 4)
A31909
Left Power Supply Unit on CPU Rack (Rack 4)
A31910
Right Power Supply Unit on CPU Rack (Rack 5)
A31911
Left Power Supply Unit on CPU Rack (Rack 5)
A31912
Right Power Supply Unit on CPU Rack (Rack 6)
A31913
Left Power Supply Unit on CPU Rack (Rack 6)
A31914
Right Power Supply Unit on CPU Rack (Rack 7)
A31915
Left Power Supply Unit on CPU Rack (Rack 7)
516
Function
ON: A duplex error occurred in the
other CPU Unit when entering
Duplex Mode. The "other CPU Unit"
indicates the standby CPU Unit for
the active CPU Unit and the active
CPU Unit for the standby CPU Unit.
ON: The CPU Units were not the
same model when entering Duplex
Mode.
ON: The unit version of the standby
CPU Unit is earlier than the unit ver-
sion of the active CPU Unit and the
active CPU Unit uses function not
supported by the standby CPU Unit.
ON: The duplex Inner Boards in the
two Process-control CPU Units were
not the same model when entering
Duplex Mode.
ON: The parameter area in the two
CPU Units in duplex mode do not
have the same contents.
ON: There is no active CPU Unit for
CPU Unit set for standby operation
when power was turned ON in
duplex mode. This occurs when one
of the following is detected: The
active CPU Unit is not mounted, the
CPU Unit switch is set to NO USE,
or pin 7 on the DIP switch is set for
simple backup operation.
ON: The user program in the two
CPU Units in duplex mode do not
have the same contents.
Settings
Status
after
mode
change
ON: Verification
Cleared
error
OFF: Normal
ON: Verification
Cleared
error
OFF: Normal
ON: Verification
error
OFF: Normal
ON: Verification
error
OFF: Normal
ON: Verification
error
OFF: Normal
ON: No active
Cleared
CPU Unit
OFF: Normal
ON: Verification
Cleared
error
OFF: Normal
ON: Power Sup-
Cleared
ply Unit error
OFF: Normal
Appendix B
Status at
Timing
Related
startup
flags,
settings
Cleared
When
A31600
error
occurs
Cleared
When
error
occurs
Cleared
When
power is
turned ON
Cleared
When
error
occurs
Cleared
When
A31602
error
occurs