Error Processing
Troubleshooting Table
Error
Program-
Error
ming
flags in
Console
Auxiliary
display
Area
I/O Bus
I/O BUS
A40114:
*
error
I/O Bus
ERR
Error Flag
I/O BUS
A40114:
ERR B
I/O Bus
Error Flag
or
I/O BUS
ERR C
Unit/Rack
UNIT NO.
A40113:
Number
DPL ERR
Duplica-
Duplica-
tion Error
tion error
Flag
RACK
NO. DPL
ERR
Too Many
TOO
A40111:
I/O Points
MANY I/O
Too Many
error
PNT
I/O Points
Flag
I/O Table
I/O SET
A40110:
Setting
ERR
I/O Set-
error
ting Error
Flag
402
For the following errors, operation will stop for a Duplex CPU System in
Duplex Mode or in Simplex Mode, or for a Single CPU System.
Error
Flags
code (in
and word
A400)
data
80C0 to
A404: I/O
Error has occurred in the bus line
80C7, or
Bus Error
between the CPU and I/O Units.
80CF
Slot and
A40400 to A40407 contain the
Rack
error slot number (00 to 09) in
Numbers
binary. 0F indicates that the slot
cannot be determined.
A40408 to A40415 contain the
error rack number (00 to 07) in
binary. 0F indicates that the rack
cannot be determined.
80CC,
A404: I/O
I/O bus error B: The CPU Units are
80CB
Bus Error
not mounted to a Duplex CPU
Slot and
Backplane.
Rack
I/O bus error C: The cable to an
Numbers
Expansion Rack is wired incor-
rectly.
A40400 to A40407: 0F hex
A40408 to A40415:
0B hex: I/O bus error B
0C hex: I/O bus error C
80E9
A410:
The same number has been allo-
CPU Bus
cated to more than one CPU Bus
Unit
Unit.
Duplicate
Bits A41000 to A41015 correspond
Number
to unit numbers 0 to F.
Flags
A411 to
The same number has been allo-
A416:
cated to more than one Special I/O
Special
Unit.
I/O Unit
Bits A41100 to A41615 correspond
Duplicate
to unit numbers 0 to 95.
Number
Flags
80EA
A409:
The same I/O word has been allo-
Expan-
cated to more than one Basic I/O
sion Rack
Unit.
Duplicate
Rack
Number
An Expansion I/O Rack's starting
word address exceeds CIO 0901.
The corresponding bit in A40900 to
A40907 (Racks 0 to 7) will be
turned ON.
80E1
A407: Too
The probable causes are listed
Many I/O
below. The 3-digit binary value (000
Points,
to 101) in A40713 to A40715 indi-
Details
cates the cause of the error. The
value of these 3 bits is also output
to A40700 to A40712.
1. The total number of I/O points
set in the I/O tables exceeds the
maximum allowed for the CPU
Unit (bits: 000).
2. The number of Expansion
Racks exceeds the maximum
(bits: 101).
80E0
---
Input and output word allocations
do no agree with input/output words
required by Units actually mounted.
Probable cause
Try turning the power OFF and ON
again.
If the error isn't corrected, turn the
power OFF and check cable connec-
tions between the I/O Units and
Racks.
Check for damage to the cable or
Units.
Correct the cause of the error and
then turn the Rack's power supply
OFF and then ON again.
Turn OFF the power supply and
replace the Backplane with a CS1D-
B@@@@ Backplane.
Correct the cable connections.
Check the unit numbers, eliminate the
duplications, and turn the Rack's
power supply OFF and then ON
again.
Check the unit numbers, eliminate the
duplications, and turn the Rack's
power supply OFF and then ON
again.
Check allocations to Units on the rack
number whose bit in ON in A40900 to
A40907. Correct the allocations so
that no words are allocated more than
once, including to Units on other
Racks, and turn the Rack's power
supply OFF and then ON again.
Check the first word setting for the
Rack indicated in A40900 to A40907
and change the setting to a valid word
address below CIO 0901 with a Pro-
gramming Device.
Correct the problem indicated by the
content of A407 and turn the power
OFF and ON again.
Check the I/O table with I/O Table Ver-
ification operation. When the system
has been corrected, register the I/O
table again.
Section 10-2
Possible remedy

Advertisement