Specific PLC Setup Settings
Power OFF Detection Time (Power OFF Detection Delay Time)
Address in
Programming
Console
Word
Bit(s)
225
0 to 7
00 to 0A hex:
0 to 10 ms
(1-ms units)
Default: 00 hex
Power OFF Interrupt Disable (Single CPU Systems Only)
Address in
Programming
Console
Word
Bit(s)
225
15
0: Disabled
1: Enabled
Default: 0
6-2-4

SIOU Refresh Tab Page

198
Settings
This setting determines how much of a
delay there will be from the detection of a
power interruption (approximately 10 to
25 ms for AC power and 2 to 5 ms for DC
power after the power supply voltage drops
below 85% of the rated value) to the confir-
mation of a power interruption. The default
setting is 0 ms.
If enabled, the power OFF interrupt will be
executed after a power interruption is con-
firmed (see note). If the power OFF interrupt
is not enabled, the CPU Unit will be reset
and operation will stop.
Note Single CPU Systems only.
Settings
When this setting is set to 1, the power OFF
interrupt task will be executed when power
is interrupted.
Note This setting cannot be used with Duplex CPU Systems.
Function
Function
Section 6-2
Related
New set-
flags and
ting's effec-
words
tiveness
---
At startup or
at the start of
operation.
(Can't be
changed dur-
ing opera-
tion.)
Related
New set-
flags and
ting's effec-
words
tiveness
---
Takes effect
at startup or
at the start of
operation.
(Can't be
changed dur-
ing opera-
tion.)