Omron CS1D DUPLEX SYSTEM - 10-2009 Operation Manual page 472

Cs1d duplex system
Table of Contents

Advertisement

Online Replacement of I/O Units, Special I/O Units, and CPU Bus Units
Basic Procedure
Initial
display
Example Procedure
1,2,3...
436
CH
FUN
SHIFT
*DM
*EM
EM_/EXT
CF
Rack
Slot
No.
No.
SRCH
DEL
Remove
Mount
Unit
Unit
INS
1. Connect a Programming Console to the peripheral port on the active CPU
Unit.
2. Access the I/O table creation display from the initial display by pressing the
keys shown below.
FUN
SHIFT
3. Select online replacement by pressing the EXT Key.
To exit online replacement, go to step 7. To start online replacement, con-
tinue to step 4.
4. Specify the number of the Rack and the slot where the Unit is to be re-
placed.
In this example, slot 8 on Rack 5 is used. In 5-8=I32 in the following dis-
plays, 5 is the rack number, 8 is the slot number, and I32 is the Unit type.
1. Display the initial display
for the I/O table creation
operation.
2. Select online
replacement.
3. Specify the Rack and slot
of the Unit to be replaced.
4. Start the online
replacement.
5. Replace the Unit.
6. Complete the online
replacement operation.
000000 CT**
CLR
000000 I/O TBL ?
CH
*DM
Replace?
*EM
?-?=
EM_/EXT
Replace?
5
5-?=
Replace?
8
5-8=
Replace?
CF
SRCH
5-8=I32
Section 11-4

Advertisement

Table of Contents
loading