Specifications of Basic I/O Units and High-density I/O Units
CS1W-OD291 Transistor Output Unit (96 Points, Sinking)
Rated Voltage
Operating Load Voltage
Maximum Load Current
Maximum Inrush Current
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
Insulation Resistance
Dielectric Strength
No. of Circuits
Internal Current Consumption 480 mA max. at 5 V DC
Fuses
External Power Supply
Weight
Accessories
Circuit Configuration
Terminal Connections
Note The maximum load currents will be 1.0 A/common and 6.0 A/Unit if a pressure-welded connector is
used.
12 to 24 V DC
10.2 to 26.4 V DC
0.1 A/point, 1.2 A/common, 7.2 A/Unit (See note.)
1.0 A/point, 10 ms max.
8.0 A/common, 10 ms max.
0.1 mA max.
1.5 V max.
0.5 ms max.
1.0 ms max.
20 M between the external terminals and the GR terminal (100 V DC)
1,000 V AC between the external terminals and the GR terminal for 1 minute at a leakage
current of 10 mA max.
96 points (16 points/common, 6 commons)
3 A (1 per common, 6 total)
The fuse cannot be replaced by the user.
10.2 to 26.4 V DC, 100 mA max.
320 g max.
Two connectors for external wiring (soldered)
Fuse
SW
Indicator
switch circuit
Output indicator
Blown fuse
detection
ERR indicator
circuit
Fuse
The ERR indicator will light if a fuse blows or if the external power supply is turned OFF,
and the corresponding Flag in the Basic I/O Unit Information Area (A050 to A089) will turn
ON.
Refer to Figure 2.
When wiring, pay careful attention to the polarity. The load may operate if the polarity is
reversed.
10.2 to
26.4 VDC
OUT00
3 CN1 circuits
to
OUT15
COM
10.2 to
26.4 VDC
OUT00
3 CN2 circuits
to
OUT15
COM
Appendix A
479