Omron CS1D DUPLEX SYSTEM - 10-2009 Operation Manual page 495

Cs1d duplex system
Table of Contents

Advertisement

Replacing the Duplex Unit
4. Set the Duplex Unit's DPL Switch to USE. Verify that the ACTIVE and CPU
STATUS Indicators for the active CPU Unit are both lit on the front of the
Duplex Unit.
Duplex Unit
Standby CPU
Active CPU
5. Verify that the new Duplex Unit's Duplex Setting Switches (DPL SW) are
set to DPL, and press the Initial (INIT) Button. When the Initial Button is
pressed, the DPL STATUS and CPU STATUS Indicators flash green and
then stay lit when operation restarts in Duplex Mode.
DPL02D
D P L S T A T U S
A C T IV E
R
C P U S T A T U S
A C T IV E
L
C P U S T A T U S
Set the DPL Switch to USE.
DPL
USE
NO USE
Verify that the Duplex Unit's ACTIVE
and CPU STATUS LED Indicators are
both lit for the active CPU Unit.
C S
The DPL STATUS indicator will flash.
When it stops flashing and remains lit,
operation will restart in Duplex Mode.
Section 11-7
DPL
USE
NO USE
459