Omron CS1D DUPLEX SYSTEM - 10-2009 Operation Manual page 622

Cs1d duplex system
Table of Contents

Advertisement

CJ1W-CIF11 RS-422A Converter
3. Strip the sheath off the signal wires to a length sufficient to attach crimp terminals. Apply vinyl tape or heat-
shrinking tube to the sheathes and stripped parts of communications lines.
4. Attach ferrules to ends of the signal lines and crimp them using a crimp tool.
• Recommended crimp terminals:
Phoenix Contact
AI Series
AI-0.5-8WH-B (serial number: 3201369)
• Recommended crimp tool:
Phoenix Contact ZA3
With four-wire cables, insert two signal lines into each crimp terminal together before crimping.
• Recommend crimp terminals:
Phoenix Contact
AI Series
AI-TWIN2 0.5-8WH (serial number: 3200933)
• Recommended crimp tool:
Phoenix Contact
UD6 (serial number: 1204436)
5. Connect the signal lines and the shield line to the RS-422A/485 terminal block.
586
Appendix G