Specific PLC Setup Settings
Duplex Settings
Operation Settings, Run under Duplex Initial
Address in
Programming
Console
Word
Bit(s)
123
14
0: Do not run during
initialization (start
running after initial-
ization
1: Start running dur-
ing initialization
Default: 0
When an operation switching error occurs in the Active CPU Unit, the Standby CPU Unit will become
the Active CPU Unit and start operating.
Address in
Programming
Console
Word
Bit(s)
125
13
0: No check (When
there is an error in
the Active CPU Unit
at startup, the
Standby CPU Unit
stays in standby sta-
tus.)
1: Check performed
(When there is an
error in the Active
CPU Unit at startup,
the Standby CPU
Unit becomes the
Active CPU Unit and
starts operating.)
Default: 0
214
Settings
This setting determines where operation is
started while the duplex system is being ini-
tialized.
In Duplex Mode, duplex initialization starts
after the power supply is turned ON. Nor-
mally, operation will begin only after initial-
ization has been completed. This setting
can be used to start operation before initial-
ization has been completed. Use this setting
to reduce startup time when the power is
turned ON.
Settings
This setting determines whether the
Standby CPU Unit will become the Active
CPU Unit and starts operating if an error is
detected in the Duplex CPU Unit set as the
Active Unit when the power is turned ON.
This setting is enabled when the Duplex
system is set to Start under Duplex Initial.
Note
1. This setting can be used in all of the Duplex CPU Unit versions.
2. This setting can be selected with CX-Programmer version 6.1 or higher.
Function
Function
Section 6-2
Related
New set-
flags and
ting's effec-
words
tiveness
---
At startup
Related
New set-
flags and
ting's effec-
words
tiveness
---
At startup