Specifications of Basic I/O Units and High-density I/O Units
CS1W-MD292 24-V DC Input/Transistor Output Unit (48/48 Points, Sourcing)
Outputs (CN1)
Rated Voltage
Operating Load Voltage
Range
Maximum Load Current
Maximum Inrush Cur-
rent
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Fuses
External Power Supply
Insulation Resistance
Dielectric Strength
Internal Current Con-
sumption
Weight
Accessories
The ERR indicator will light if a fuse blows or if the external power supply is turned OFF, and the
corresponding Flag in the Basic I/O Unit Information Area (A050 to A089) will turn ON.
Terminal Connections
12 to 24 V DC
10.2 to 26.4 V DC
0.1 A/point, 1.2 A/common,
3.6 A/Unit (See note 2.)
1.0 A/point, 10 ms max.
8.0 A/common, 10 ms max.
0.1 mA max.
1.5 V max.
0.5 ms max.
1.0 ms max.
48 points (16 points/common, 3
commons)
3 A (1 per common, 3 total)
The fuse cannot be replaced by
the user.
10.2 to 26.4 V DC, 50 mA min.
20 M between the external terminals and the GR terminal (100 V DC)
1,000 V AC between the external terminals and the GR terminal for 1 minute at a leakage cur-
rent of 10 mA max.
350 mA max. at 5 V DC
320 g max.
Two connectors for external wiring (soldered)
SW
Indicator
switch circuit
Output indicator
Blown fuse
detection
ERR indicator
circuit
4.7 k
1000 pF
560
Refer to Figure 5.
When wiring, pay careful attention to the polarity. The load may operate if the polarity is
reversed.
Inputs (CN2)
Rated Input Voltage
Allowable Input Voltage
Range
Input Impedance
Input Current
ON Voltage/ON Current
OFF Voltage/OFF Cur-
rent
ON Response Time
OFF Response Time
No. of Circuits
Number of Input Simul-
taneous ON
COM (+V)
OUT00
3 CN1 (Output)
to
OUT15
0 V
IN00
to
3 CN2 (Input)
IN15
COM
Appendix A
24 V DC
20.4 to 26.4 V DC
4.7 k
Approx. 5 mA (at 24 V DC)
17 V DC min./3 mA min.
5 V DC max./1 mA max.
8.0 ms max. (Possible to select
one out of eight times from 0 to
32 ms in the PLC Setup.) (See
note 1.)
8.0 ms max. (Possible to select
one out of eight times from 0 to
32 ms in the PLC Setup.) (See
note 1.)
48 points (16 points/common, 3
commons)
50% (8 points/common) (at 24 V
DC) (Depends on ambient tem-
perature.)
493