Error Displays - Omron CS1D DUPLEX SYSTEM - 10-2009 Operation Manual

Cs1d duplex system
Table of Contents

Advertisement

Online Replacement of I/O Units, Special I/O Units, and CPU Bus Units

11-4-3 Error Displays

Starting Online
Replacement
Specifying an Empty Slot
Error Displays when Ending Online Replacement
When the online replacement procedure for the last Unit has been ended, the
display will not change even if the INS Key is pressed. If the INS Key is
pressed without pressing the Down Key, the Units for which online replace-
ment procedures have been started can be displayed without ending the pro-
cedures.
Errors can occur when starting and stopping online replacement procedures.
These are described in this section.
DEL
• The following display will appear if a different type of Unit is mounted from
the one that was removed.
• It is also displayed if the unit number (UNIT No./MACH No.) is different
from the Unit that was removed.
• The following display will appear if the node number is different from the
Unit that was removed (for online replacement of a Duplex Controller Link
Unit or Duplex Ethernet Unit).
The CLR Key can be pressed to display the Unit registered in the I/O tables
and the Unit that was mounted.
The display on the left is the registered Unit and the display on the right is the
Unit that is currently mounted.
Replace End
3-2=M96
Replace End?
INS
~5-8=I32
Replace End?
INS
~0-4=O32
Replace End?
INS
~3-2=M96
Replace End?
INS
~5-8=I32
Replace Start?
5-8=*****
Replace End?
DIFFERENT UNIT
Replace End?
NETWORK DPL ERR
Section 11-4
441