Mounting Height - Omron CS1D DUPLEX SYSTEM - 10-2009 Operation Manual

Cs1d duplex system
Table of Contents

Advertisement

Installation
5-2-3

Mounting Height

156
Input duct
CPU Rack
Expansion Rack
Fuses, relays, timers, etc.
(NOT heat-generating equip-
ment, power equipment, etc.)
The mounting height of CPU Racks and Expansion Racks is 123 to 153 mm,
depending on I/O Units mounted. If Programming Devices or connecting
cables are attached, the additional dimensions must be taken into account.
Allow sufficient clearance in the control panel in which the PLC is mounted.
123 to 153 mm
Approx. 180 to 223 mm
Output duct
200 mm min.
Breakers,
fuses
Power
equipment
such as
transformers
and magnetic
relays
Terminal
Terminal blocks for
blocks or PLC
power equipment
Section 5-2
Power duct