Specific PLC Setup Settings
Enable Setting in Word 83 for Inner Boards (Single CPU Systems Only)
Address in
Programming
Console
Word
Bit(s)
84
15
0: Wait for Boards.
1: Don't wait.
Default: 0
6-2-2

CPU Unit Tab Page

Execute Process
Detect Low Battery
Address in
Programming
Console
Word
Bit(s)
128
15
0: Detect
1: Do not detect
Default: 0
Settings
To start the CPU Unit in MONITOR or PRO-
GRAM mode even if there is one or more of
Boards that has not completed startup pro-
cessing, set this setting to 1 (Don't wait for
Boards).
To wait for all Boards to finish startup process-
ing, set this setting to 0 (Wait for Boards).
This setting is valid only if the Startup Condi-
tion is set to 1 (Don't wait for Units and
Boards).
Note This setting cannot be used with Duplex CPU Systems.
Settings
This setting determines whether CPU Unit
battery errors are detected. If this setting is
set to 0 and a battery error is detected, the
ERR/ALM indicator on the CPU Unit will
flash and the Battery Error Flag (A40204)
will be turned ON, but CPU Unit operation
will continue.
Function
Function
Section 6-2
Related
New set-
flags and
ting's effec-
words
tiveness
---
At startup
Related
New set-
flags and
ting's effec-
words
tiveness
A40204 (Bat-
Takes effect
tery Error
the next cycle
Flag)
193