Omron CS1D DUPLEX SYSTEM - 10-2009 Operation Manual page 271

Cs1d duplex system
Table of Contents

Advertisement

Allocating First Words to Racks
Word Allocations
Rack number 0
Rack number 1
Rack number 2
Rack number 3
For Racks in which the first word address has been set, words are allocated to
Units in the order that the Units are mounted (from left to right) beginning with
the specified first word. Words are not allocated to empty slots.
For Racks in which the first word address has not been set, words are allo-
cated in rack-number order (lowest to highest) continuing from the last word
allocated to the previous rack and starting with CIO 0000 on the first Rack for
which the first word is not set.
Example: Setting the First Words for Racks
In this example, the first words have been set for Racks 0 (the CPU Rack), 2,
and 3. For simplicity, only 16-bit Units have been used.
First word: CIO 0100
0
1
2
3
4
CIO
CIO
CIO
CIO
CIO
0100
0101
0102
0103
0104
First word: CIO 0200
0
1
2
3
4
CIO
CIO
CIO
CIO
0200
0201
0202
0203
No first word setting (Words automatically allocated in order from CIO 0000.)
0
1
2
3
4
CIO
CIO
CIO
CIO
CIO
0000
0001
0002
0003
0004
First word: CIO 0300
0
1
2
3
4
CIO
CIO
CIO
CIO
CIO
0300
0301
0302
0303
0304
Rack First Word Settings
Rack
CPU Rack
Rack 1
Rack 2
Rack 3
Note Rack numbers (0 to 7) are fixed according to the order that the Racks are
physically connected with cable. The CPU Rack is always Rack 0 and the
other Racks are, in order, Racks 1 to 7. These numbers cannot be changed.
In the above example, the shaded Racks are allocated words starting from the
5
6
7
CIO
CIO
CIO
0105
0106
0107
5
6
7
8
CIO
CIO
CIO
CIO
0204
0205
0206
0207
5
6
7
8
CIO
CIO
CIO
CIO
0005
0006
0007
0008
5
6
7
8
CIO
CIO
CIO
CIO
0305
0308
0306
0307
First word
CIO 0100
CIO 0200
Not set
CIO 0300
Section 7-3
CPU Rack
CS1D Expansion Rack
CS1D Expansion Rack
CS1D Expansion Rack
235