Omron CS1D DUPLEX SYSTEM - 10-2009 Operation Manual page 440

Cs1d duplex system
Table of Contents

Advertisement

Error Processing
Errors for which Duplex
Mode Continues
Troubleshooting Table
Error
Program-
Error
ming Con-
flags in
sole
Auxiliary
display
Area
Duplex
PS ERROR
A31602,
power
x-y
A40214
supply
x = Rack #
error
y = Slot
Duplex
NET DPL
A31603,
*
communi-
A40214
ERR
cations
*
= Node
error
address
System
SYS FAIL
A40215:
FAL error
FAL
FAL Error
Flag
PLC
PC SETUP
A40210:
Setup
ERR
PLC
error
Setup
Error Flag
I/O Table
I/O VRFY
A40209:
Verifica-
ERR
I/O Verifi-
tion error
cation
Error Flag
Non-fatal
NO-FTL
A40208:
Inner
INNER
Inner
Board
ERR
Board
error
Error Flag
404
If any of the following errors occurs for a Duplex CPU System in Duplex Mode,
operation will continue in Duplex Mode and in RUN or MONITOR mode. Oper-
ation will also continue if any of these errors occurs in Simplex Mode or in a
Single CPU System.
A non-fatal error has occurred if the indicators have the following conditions
during operation in RUN or MONITOR mode.
Power Supply Unit
POWER
CPU Unit
RUN
ERR/ALM
INH
PRPHL
COMM
Duplex Unit (with
DPL STATUS
error occurring on
Active CPU Unit
active CPU Unit)
indicators
Standby CPU Unit
indicators
For all of the following errors, operation will continue if the error occurs for a
Duplex CPU System in Duplex Mode or in Simplex Mode, or for a Single CPU
System. If it occurs in Duplex Mode, operation will continue in Duplex Mode.
Error
Flags
code (in
and
A400)
word
data
0003
A319,
An error has occurred in one of the
A320
Power Supply Units.
• The primary-side power supply
has been interrupted.
• The secondary-side voltage has
dropped below 5 V or is an over-
voltage.
0600 to
A434 to
An error has occurred for a Commu-
060F
A437
nications Unit (Controller Link Unit)
with a unit number that was set for
Right-
duplex operation.
most
digit is
unit No.
4101 to
A360 to
FAL(006) has been executed in pro-
42FF
A391:
gram.
Exe-
Executed FAL Number Flags
cuted
A36001 to A39115 correspond to
FAL
FAL numbers 001 to 511.
Number
The error code in A400 will indicate
Flags
the FAL number. The leftmost digit of
the code will be 4 and the rightmost
3 digits of the code will be from 100
to 2FF hex and will correspond to
FAL numbers 001 to 511.
009B
A406:
There is a setting error in the PLC
PLC
Setup. The location (binary offset) of
Setup
the error is written to A406.
Error
Location
00E7
---
A Unit has been added or removed,
so the registered I/O tables don't
agree with the actual Units in the
PLC.
The I/O Verification Error Flag goes
OFF when the situation is corrected.
02F0
A424:
An error occurred in the Duplex Inner
Inner
Board
Board
Error
Informa-
tion
ACTIVE
CPU STATUS
ACTIVE
CPU STATUS
Probable cause
Use A319 and A320 to identify the
Power Supply Unit with an error and
either correct the error or, if neces-
sary, replace the Unit.
Use A434 and A437 to identify the
Communications Unit with an error
and either correct the error or, if nec-
essary, replace the Unit.
Correct according to cause indicated
by FAL number (set by user).
Change the indicated setting to a
valid setting.
Execute the I/O Table Verify opera-
tion to find the problem location. Cre-
ate new I/O tables or replace the Unit
to match the registered I/O tables.
Check the Inner Board indicators.
Refer to the Duplex Inner Board's
operation manual for details.
Section 10-2
Lit green
Lit green
Flashing red
----
----
----
Lit green
Lit green
Lit green
Not lit
Lit green
Possible remedy